試験高合格率保証2026年10月08日 H20-923_V1.0試験問題と正確な回答! [Q37-Q59]

Share

試験高合格率保証2026年10月08日 H20-923_V1.0試験問題と正確な回答!

テストエンジン練習問題H20-923_V1.0有効最新の問題集

質問 # 37
When a critical alarm is generated for the unit, the indicator on the LCD controller turns red and the buzzer beeps continuously.

  • A. True
  • B. False

正解:A

解説:
In Huawei data center facility equipment (such as precision cooling units and related controllers), alarm presentation follows a clear severity-based design so technicians can recognize urgency immediately without entering detailed menus. Acritical alarmrepresents the highest severity level and is treated as a condition that may impact safe operation, cooling continuity, or equipment protection. For this reason, the LCD controller uses the most prominent visual and audible indications: theindicator turns redto show critical severity, and thebuzzer sounds continuouslyto ensure the alarm cannot be overlooked in a noisy equipment-room environment. This behavior supports rapid response: O&M personnel can quickly identify that immediate action is required, then open the alarm list to locate the root cause, confirm whether the unit has derated or stopped, and execute the prescribed troubleshooting steps (for example, checking power status, sensor readings, fan/compressor status, water flow/pressure, and protection interlocks). Therefore, the statement correctly describes the standard critical-alarm indication method on the LCD controller.


質問 # 38
Video management can connect to the third-party video surveillance subsystem and play historical videos.

  • A. True
  • B. False

正解:A

解説:
In Huawei's data center O&M architecture, video is treated as an important auxiliary capability for security and remote operation. TheVideo Managementfunction is designed not only to view live camera feeds, but also to integrate video resources into the same O&M workflow as alarms, access control events, and environmental monitoring. In typical deployments, the actual video storage and recording are handled by athird-party video surveillance subsystem(for example, an NVR/VMS platform). Huawei's video management function can connect to that third-party subsystem so that camera resources can be accessed in a unified interface, allowing operators to perform linkage operations such as "view video on alarm" and routine security inspection without switching platforms. Because historical recordings are stored by the surveillance subsystem, once the integration is established and permissions are correctly configured, operators can retrieve andplay back historical videofor event tracing, audit, and incident investigation. This supports closed-loop O&M: alarm/event occurs # video verification # root-cause confirmation # maintenance action # evidence retention.


質問 # 39
After replacing the fan, choose "Menu > _____ > Performance Maintenance" on the main screen to enter the
"Performance Maintenance" screen and clear the accumulated runtime of the indoor fan.

  • A. Alarms
  • B. Running
  • C. Maint
  • D. Settings

正解:C

解説:
In Huawei room air conditioner and precision cooling unit O&M, fan replacement is treated as a maintenance activity that must be recorded in the controller so lifecycle management remains accurate. The controller tracksaccumulated runtimefor wear components such as indoor fans to support preventive maintenance planning, alarm thresholds, and performance analysis. After a fan is replaced, the old runtime value must be cleared so the system can correctly measure the new fan's service hours, avoiding premature "maintenance due" prompts or misleading reliability assessments. This function belongs to themaintenancefunction set rather than alarm viewing, parameter settings, or basic running status. Therefore, the correct navigation is throughMenu > Maint > Performance Maintenance, where the technician can locate the indoor fan runtime item and reset/clear it after confirming the replacement. Performing this step ensures consistent O&M records, supports correct maintenance intervals, and helps troubleshooting by aligning future fan-related alarms with the actual operating hours of the newly installed component.


質問 # 40
Which of the following statements is false about how to start an electric heater?

  • A. When "Low temperature heating" is selected, the electric heater determines whether to start only based on the temperature requirements no matter whether the dehumidification function is enabled.
  • B. When "Dehumidification heating", "Low temperature heating", or "Dehumidification & Low temperature heating" is selected, if the temperature in the equipment room is low, the air conditioner automatically starts the heating function to meet the temperature control requirements of the equipment room.
  • C. If "Dehumidification & Low temperature heating" is selected, the electric heater determines whether to start based on the temperature requirements when the dehumidification or heating conditions are met.
  • D. When "Dehumidification heating" is selected, the electric heater determines whether to start based on the current temperature only when the dehumidification function is enabled.

正解:B

解説:
Huawei precision cooling logic separates heater enablement into distinct control strategies to avoid unnecessary heating and to keep humidity control stable. InLow temperature heating, the heater is governed purely by the room temperature control demand: if temperature is below the heating threshold (or below setpoint with heating conditions met), the heater can start regardless of whether dehumidification is enabled, which matches statement D. InDehumidification heating, the heater is not a general low-temperature heater; it is an auxiliary function used to prevent overcooling during dehumidification and to maintain temperature while the unit dehumidifies. Therefore, the heater in this mode is permitted to start only when thedehumidification function is activeand temperature conditions require compensation, which matches statement B. Statement C is false because it incorrectly claims thatanyof the three selections will start heating automatically whenever room temperature is low; that is not true for "Dehumidification heating" unless dehumidification is actually enabled and running.


質問 # 41
Which of the following interfaces is used to connect the controller and the main control module of the unit?

  • A. USB
  • B. SW
  • C. DP
  • D. I2C/12v

正解:D

解説:
In Huawei precision cooling units, the LCD controller (human-machine interface) must exchange real-time operating data and commands with the unit's main control module while also receiving a stable low-voltage power supply. This connection is typically implemented as alow-voltage communication bus plus DC power, which is why the interface is identified asI2C/12V. TheI2Cportion provides the data channel used for status display, parameter viewing/setting (within permission scope), alarm presentation, and command delivery (such as mute, reset, or control enable actions). The12 Vportion supplies power to the controller so it can operate independently of high-voltage power circuits and remain safe to access during routine O&M.
Interfaces likeDPandUSBare not used as the internal control link between the HMI and the main control board in this type of unit, and "SW" is not the designated controller-to-main-board interface in the standard wiring definition. Therefore,I2C/12Vis the correct selection.


質問 # 42
ECO mode is not recommended when the load is less than

  • A. 10%
  • B. 5%
  • C. 30%
  • D. 20%

正解:D

解説:
ECO mode is designed to improve UPS efficiency by supplying the load mainly through the static bypass path when the mains is within the acceptable quality window, while keeping the inverter synchronized and ready to take over quickly if power quality degrades. However, when the load istoo light, the overall operating characteristics of the UPS system are less favorable for ECO operation. At low load levels, the benefits of ECO in reducing conversion losses are smaller, and the system becomes more sensitive to frequent transfers caused by minor mains fluctuations, which can increase transfer##and operational risk. In addition, very light loads can reduce the effectiveness of system self-check behaviors and may lead to less stable operating margins for parallel systems, power modules, and downstream distribution, depending on site conditions.
Therefore, Huawei O&M guidance sets a practical threshold and states thatECO mode is not recommended when the load is lower than 20%, helping ensure stable operation, fewer unnecessary transfers, and better overall power supply reliability for critical loads.


質問 # 43
When the outdoor unit is installed at a position higher than the indoor unit, install an oil trap every five to six meters in the vertical direction along the gas pipe to ensure system reliability.

  • A. True
  • B. False

正解:A

解説:
This statement is true. In split DX/precision cooling refrigerant systems, the "gas pipe" typically refers to thesuction linereturning refrigerant vapor (and entrained compressor oil) from the indoor evaporator to the outdoor unit/compressor. When theoutdoor unit is higher than the indoor unit, the suction line includes avertical riser. Oil naturally tends to settle and flow downward under gravity, so without proper piping measures, oil may accumulate in low points or fail to be carried upward consistently, leading topoor oil return.
Insufficient oil return can cause compressor lubrication issues, abnormal noise, overheating, reduced efficiency, and long-term reliability risks. Installingoil trapsat the bottom of the riser and thenevery 5-6 metersof vertical lift helps collect oil and allows it to be periodically swept upward by refrigerant velocity, maintaining stable oil circulation. This requirement is especially important in data center cooling because continuous operation and high availability demand reliable compressor lubrication and stable refrigerant flow under varying load conditions.


質問 # 44
The NetEco service program backend can be accessed through the iBMC port.

  • A. False
  • B. True

正解:A

解説:
In Huawei data center facility management,NetEcois the management software platform (server/application) used to centrally monitor and manage sites, whileiBMCis the out-of-band hardware management interface used forserver remote maintenance(such as power control, hardware health, BIOS settings, and remote console) on the specific server where iBMC exists. TheiBMC port is not a service access interface for NetEco. NetEco's backend services are accessed through theserver operating system network interfaces (management/service network) and corresponding application ports after the server is properly networked and configured. Even if NetEco is deployed on a Huawei server that has iBMC, iBMC only provides a channel to manage the server hardware and does not expose NetEco application access as an official commissioning
/O&M path. Therefore, NetEco backend access should be planned via the site's management network (IP addressing, routing, security policy), not via iBMC.


質問 # 45
In a data center fire protection design, which approach best matches Huawei facility practice for protecting IT rooms while minimizing secondary damage to IT equipment?

  • A. Install a water sprinkler system as the only suppression method inside the IT white space
  • B. Disable automatic suppression to avoid accidental discharge
  • C. Deploy a smoke detection system plus a clean-agent gas extinguishing system with interlock controls for automatic release
  • D. Use only portable extinguishers and rely on manual response

正解:C

解説:
Huawei data center facility design typically follows a layered fire protection concept: early detection, controlled alarm linkage, and suppression methods that protect equipment and ensure personnel safety.
A smoke detection system (often combined with staged alarms) provides early warning so operators can verify events and initiate emergency procedures. For the IT white space, a clean-agent gas extinguishing system is preferred because it suppresses fire without leaving residue and significantly reduces the risk of corrosion or contamination compared with powder-based agents. The extinguishing system is normally integrated with linkage/interlock controls: audible/visual pre-discharge alarms, time delay, emergency abort, door access control logic, and HVAC shutdown or damper control to help maintain agent concentration. This coordinated mechanism reduces false discharge risk while preserving a reliable automatic response if a real fire develops. In contrast, relying only on manual extinguishers is too slow for rapid fire growth, and water sprinklers alone can cause substantial collateral damage to servers and power equipment.


質問 # 46
Which of the following can be used to start the inverter of the UPS5000-H?

  • A. NetEco
  • B. ECC
  • C. UPS LCD
  • D. UPS WebUI

正解:C、D

解説:
For the Huawei UPS5000-H, inverter startup is executed through theUPS's own control interfaces, which provide the "Running Control / Inv. ON" operation with the required confirmations and permissions. TheUPS LCD (MDU touchscreen)supports inverter startup through menu operations such as selecting inverter start functions and confirming the action after authentication. TheUPS WebUIalso provides the same operational control path, where an operator logs in and issues theInv. ONcommand under the UPS monitoring/running control pages. These two interfaces are part of the UPS monitoring and control design and are explicitly used for commissioning and routine O&M actions.
By contrast,ECC(data center controller) andNetEco(management platform) are mainly used for site-level monitoring, alarm collection, visualization, reporting, and centralized management. While they can display UPS status and alarms (and may integrate with UPS data), inverter startup is defined as aUPS running control operationperformed on the UPS's LCD or WebUI control plane to ensure proper authorization, safety checks, and command traceability.


質問 # 47
In an in-room solution that adopts overhead air supply through air ducts, the net height of each floor must be greater than or equal to how many meters?

  • A. 0
  • B. 1
  • C. 2
  • D. 3

正解:C

解説:
For an in-room cooling solution that usesoverhead air supply with air ducts, sufficient vertical space is required to accommodate the ductwork, airflow distribution components (such as plenums, turning vanes, flexible connectors, and diffusers), cable trays/pipes that may share the overhead route, and the necessary maintenance clearance. If the net height is too low, the duct cross-section becomes constrained, which increases airflow resistance and static pressure, reduces delivered airflow volume, and can cause uneven air distribution. This leads to hot spots, higher fan power, and difficulty maintaining stable supply/return temperature control. In Huawei data center air-conditioning design guidance, overhead ducted supply is therefore matched with aminimum net floor height requirement of 4 m, ensuring ducts can be sized correctly for the target airflow, noise, and pressure limits while preserving safe installation and maintenance space. A 3 m net height is generally suitable for non-ducted in-room layouts, but becomes insufficient once full overhead ducting is introduced.


質問 # 48
What are the colors of indicators on the LCD panel of the MDU?

  • A. Orange
  • B. Red
  • C. Green
  • D. Yellow

正解:B、C、D

解説:
On Huawei UPS systems (such as the UPS5000 series), the MDU LCD panel includes status indicators designed to provide an immediate visual understanding of the UPS operating condition and alarm severity.
The indicator system usesthree standard colors:green,yellow, andred.Greenindicates the UPS is operating normally and the power supply path is healthy.Yellowis used to show abnormal conditions that require attention, such as warnings or non-critical alarms, where the UPS can typically continue supplying power but O&M personnel should inspect and handle the issue within the required timeframe.Redindicates serious or critical conditions, such as major faults or alarms that may threaten continuous power supply or require urgent action according to operating procedures. These three colors align with the common Huawei alarm severity presentation logic on the UPS display and help technicians quickly judge whether the situation is normal, warning-level, or critical-level without entering deeper menus.Orangeis not used as an MDU indicator color in this context.


質問 # 49
When tightening the screws (M16x50 mm) for the output power cables of lithium battery cabinets, what torque should be used to tighten and verify the screws?

  • A. 80 N m
  • B. 120 N m
  • C. 100 N m
  • D. 60 N m

正解:B

解説:
For Huawei SmartLi lithium battery cabinets, the output power cable termination uses high-current DC conductors, so the mechanical fastening torque is strictly specified to ensure both safety and long-term reliability. ForM16x50 mm screwsused on the+/N/# output cable terminals, the specified tightening
/verification torque is120 N m. This torque requirement is defined to achieve the correct clamping force between the DT terminal lug and the cabinet busbar/terminal surface. If the torque is below the requirement, contact resistance increases, which can lead to abnormal heating during charge/discharge, voltage drop, alarm events, and accelerated oxidation at the joint. If the torque is excessive, it can damage threads, deform the lug or busbar contact area, and introduce hidden mechanical stress that may loosen over thermal cycles. During commissioning and routine maintenance, technicians use a calibrated torque wrench to tighten and then re- verify each connection to the specified value to prevent hotspots and ensure stable operation under peak current conditions.


質問 # 50
When the mains supply is stable, the UPS5000-H mainly works in which mode after ECO is configured?

  • A. Normal
  • B. Maintenance bypass
  • C. Battery
  • D. Static bypass

正解:D

解説:
After ECO mode is enabled on the UPS5000-H, the system's control objective changes from "always supply the load through the inverter" to "maximize efficiency while keeping protection mechanisms ready." When themains input is within the configured ECO acceptance window(voltage, frequency, THD, and other quality thresholds), the UPS supplies the critical load primarily through thestatic bypass path, which has lower conversion losses than continuous double-conversion. The inverter remains synchronized and on standby, so if the mains quality deteriorates or an abnormal condition is detected, the UPS canrapidly transferthe load back to inverter operation to maintain output stability. Battery mode is only used when the rectifier/bypass source is unavailable or out of range, and maintenance bypass is a manual service path used for isolation during maintenance, not for normal energy-saving operation. Therefore, with stable utility power and ECO configured, the UPS5000-H mainly operates instatic bypass mode.


質問 # 51
The NetEco northbound interface does not support the SNMP protocol. Only WebService interfaces are supported.

  • A. False
  • B. True

正解:A

解説:
In Huawei's data center facility management architecture, thenorthbound interfaceof NetEco is designed specifically to integrate with upper-layer systems such as enterprise NMS platforms, SOC/monitoring centers, and customer unified O&M systems. To meet common industry integration practices, NetEco northbound capabilities are not limited to only one interface type. In addition to WebService-style interfaces used for richer data exchange and structured integration, NetEco also supportsSNMP-based northbound integration, which is widely used for alarm forwarding, basic status monitoring, and interoperability with standard network management tools. SNMP is particularly common in mixed-vendor environments because it enables a lightweight and standardized method to deliver key alarms and events to a customer's central monitoring platform without requiring deep application coupling. Therefore, the statement that "only WebService interfaces are supported and SNMP is not supported" is incorrect: NetEco northbound integration supports SNMP along with other northbound interface methods depending on the integration scenario and customer requirements.


質問 # 52
After installing the FusionCol8000-C (110-440 kW), inject water to preserve the pressure for the chilled water pipes to how many MPa. After 30 minutes, check that no leakage occurs. Preserve the pressure for 24 hours. If the pressure drop is less than 0.01 MPa and no leakage occurs, the pipes do not leak.

  • A. 0.5
  • B. 1.2
  • C. 0
  • D. 0.8

正解:D

解説:
For FusionCol8000-C chilled-water systems, Huawei commissioning requires awater leakage/pressure- holding teston the chilled-water piping after installation to verify joint sealing, valve interfaces, and connection integrity before long-term operation. The specified method is toraise the water pressure in the chilled-water pipe to 0.8 MPa, then observe for30 minutesto confirm there is no visible leakage. If the system remains dry, the same pressure isretained for 24 hoursas a stability verification step. The acceptance criterion is that thepressure drop is less than 0.01 MPaover the 24-hour period and no leakage is found, which demonstrates that the piping and fittings meet tightness requirements under the prescribed test pressure. This procedure helps prevent future failures such as slow seepage, corrosion around joints, insulation waterlogging, and unexpected shutdowns caused by water loss or low differential pressure alarms. It also ensures that subsequent flushing, venting, and operational commissioning can be performed safely and reliably.


質問 # 53
After the unit is powered on for the first time, it enters the compressor preheating state. To quickly perform power-on commissioning, you can manually shut down the compressor preheating.

  • A. False
  • B. True

正解:A

解説:
Compressor preheating is a protection mechanism used during first power-on (and after long power-off periods) to improve compressor reliability before allowing refrigeration startup. The preheating function warms the compressor oil and reduces refrigerant migration and oil dilution, which otherwise can lead to liquid refrigerant in the compressor crankcase. If the compressor starts when oil is diluted or when liquid refrigerant is present, it increases the risk of abnormal noise, poor lubrication, high mechanical stress, and even liquid strike, which can damage the compressor and shorten service life. For data center cooling equipment, where continuous reliability is essential, the commissioning logic treats preheating as a required prerequisite for safe compressor operation. Therefore, O&M practice does not recommend bypassing or manually shutting down compressor preheating just to accelerate commissioning. The correct approach is to keep the unit energized and allow the preheating period to complete, then proceed with commissioning steps (fans, cooling system tests, alarms, and control verification) under proper protection conditions.


質問 # 54
The rated output capability of a single power module for the UPS5000-H is how many kVA.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

正解:A

解説:
Huawei UPS5000-H is a modular UPS platform built by paralleling standardized power modules inside the power cabinet to form different system capacities. In this architecture, the "single power module" is the basic building block that contributes a fixed rated apparent power to the total UPS capacity. For the UPS5000-H series, each power module is rated at100 kVA, and the system capacity is achieved by installing multiple 100 kVA modules and configuring redundancy (such as N+1). This modular approach improves availability and O&M efficiency because a failed module can be isolated and replaced without shutting down the entire UPS, while the remaining modules continue carrying the load within their capacity limits. Using 100 kVA as the module rating also simplifies planning: technicians can quickly estimate remaining headroom by counting active modules and comparing total available kVA/kW against the real-time load, ensuring the UPS stays within recommended loading and redundancy margins during maintenance or fault conditions.


質問 # 55
Which of the following is not a scenario-based solution for Huawei data center products?

  • A. FusionModule500
  • B. FusionDC1000
  • C. FusionModule2000
  • D. FusionDC800

正解:D

解説:
Huawei's scenario-based data center facility portfolio is organized around clearly defined solution families that map to typical deployment scenarios and site sizes. FusionModule500 and FusionModule2000 are smart modular data center solutions designed for standardized, fast deployment in equipment rooms and enterprise edge/branch scenarios.They integrate key subsystems such as power supply and distribution, cooling, monitoring, and optional fire protection into a modular architecture that reduces footprint and accelerates on- site delivery. Likewise, FusionDC1000 is Huawei's prefabricated modular data center series, delivered as complete, factory-integrated modules that combine civil engineering elements with electromechanical infrastructure for rapid construction, predictable quality, and scalable expansion across different capacity tiers. In contrast, FusionDC800 is not used as a defined scenario-based solution name within Huawei's mainstream data center facility solution lineup (where "FusionDC" offerings are represented by the FusionDC1000 series and "FusionModule" offerings by numbered FusionModule solutions). Therefore, FusionDC800 is the option that does not match Huawei's scenario-based solution naming.


質問 # 56
The frequency of power supply equipment can be 50 Hz, 60 Hz, or 70 Hz.

  • A. False
  • B. True

正解:A

解説:
In data center power systems, the utility grid frequency standard iseither 50 Hz or 60 Hz, depending on the country/region. Data center facility equipment-such as UPS systems, power distribution units, switchgear, and monitoring components-is designed to operate reliably under these standardized grid frequencies, with acceptable tolerance ranges around the nominal value. While some power conversion equipment can adapt between50/60 Hz(for example, via frequency tracking or double-conversion),70 Hz is not a standard utility frequencyused for data center facility power supply, and it is not treated as a normal operating frequency in typical design, acceptance testing, or O&M procedures. From an operations perspective, maintaining correct frequency is critical because abnormal frequency can trigger UPS transfer logic, increase losses, create synchronization issues with bypass sources, and negatively affect downstream IT loads. Therefore, stating that power supply equipment frequency "can be 50 Hz, 60 Hz, or 70 Hz" is incorrect for standard data center infrastructure practice.


質問 # 57
Which of the following control modes can be used for temperature and humidity control of smart cooling products?

  • A. Supply air
  • B. Hot aisle
  • C. Return air
  • D. Cold aisle

正解:A、C、D

解説:
Smart cooling temperature and humidity control is based on where the control "reference point" is measured and regulated.Supply air controluses the unit outlet sensor as the main reference, so the system directly regulates the temperature (and humidity when configured) of the air delivered to the IT area. This provides stable supply conditions and is widely used for predictable airflow organization.Return air controluses the unit inlet/return sensor as the reference, reflecting the heat absorbed from IT loads; it helps the unit respond to real load changes and maintain stable operation when room mixing or load distribution varies.Cold aisle controluses sensors placed in the cold aisle (near rack inlets) as the reference, aligning control with the most critical point for IT reliability-server intake conditions-especially in contained aisle scenarios.Hot aisleis generally not used as a primary temperature-and-humidity control mode because hot aisle conditions are intentionally high and variable (driven by load and containment), and controlling to hot aisle targets can conflict with ensuring stable rack inlet temperature and proper dehumidification behavior. Therefore, A, B, and C are valid control modes.


質問 # 58
Which of the following models is a Huawei in-room chilled water horizontal air supply product?

  • A. FusionCol8000-C210H
  • B. FusionCol5000-A050H
  • C. NetCol5000-A070U
  • D. NetCol8000-C070D

正解:B

解説:
Huawei room-level air conditioning products are commonly identified by the series name plus a model suffix that indicates the cooling medium and airflow form factor. Anin-room chilled waterunit uses a chilled-water coil as the primary heat-exchange component and relies on the building's chilled-water system (chiller/plant) rather than an onboard refrigeration compressor for cooling generation. "Horizontal air supply" describes the discharge direction: the unit supplies conditioned air laterally into the room or into a specific airflow organization (such as cold-aisle delivery), supporting predictable airflow paths and stable return air conditions. Within the provided options,FusionCol5000-A050His the model that matches both identifiers: it belongs to Huawei's room cooling product line and the model code indicates an in-room configuration withchilled-watercapability andhorizontalair supply orientation. The other options belong to different series or represent configurations typically associated with other deployment forms (such as different placement, airflow direction, or system architecture). Therefore, the correct selection isFusionCol5000-A050H.


質問 # 59
......